Skip to the content

The validation record

The Monju plant relation against Wu's rig, in the regime both were measured in

Tier 2: measurement on a controlled rig.

What was compared
The air-side heat transfer coefficient of a three-row bundle of annular finned tubes, as predicted by the Monju plant relation (Mochizuki and Takano, 2009, as transcribed by Wu et al.), over Reynolds numbers of 1176 to 2500, below the low-Reynolds transition.
Against
The low-Reynolds fit of Wu et al. (2024, Eq. 42) to their own wind-tunnel measurements on that bundle, with an expanded measurement uncertainty of 5.75% and a fitting deviation of 2.4%.
The agreement
The Monju relation lies within −1.0% to +4.1% of the fit, every point inside the case's tolerance of 6.2%. Above the transition, at Re 2650-4813, its high branch runs 9-12% above Wu's fit, outside the tolerance, and that range is not compared.
What it shows
The agreement shows that a relation fitted on a reactor's plant data transfers to a different bundle in the low-Reynolds regime, where the model uses it by default. It is a comparison of one closure with no tower in it, and the relation's own accuracy remains its source's (±20% on the low branch).
Source
Y. Wu, Y. Liu, Z. Zhang, Q. Xiang, Y. Sun, X. Yang, S. Jiang, 'A quick measurement method of heat transfer coefficient and friction factor for finned tube bundle of the air cooler under large temperature difference', International Journal of Heat and Mass Transfer 227 (2024) 125556Table 1 (test set I), Eq. (42), Eq. (43) as the transcription of Mochizuki & Takano [16], and the sentence equating 4000 on the heated equivalent diameter with a Reynolds number of 2646. Fig. 17 is the paper's own version of this comparison and is not digitised.