Direct natural draft, vertical bundles

Condenses turbine exhaust steam in finned-tube bundles standing around the base of a natural-draft tower.

ShellRing of delta bundlesClapboardSteam ductSection on the centre line050 mExhaust steamHeated airAir in
Figure 1. Direct natural draft, vertical bundles, in elevation: the air in blue going in and dashed red coming out heated, the hot fluid in amber. It is drawn to scale from the app's default case for the system; the app draws each case's own geometry in 3-D.

Steam condenses in vertically arranged finned-tube bundles around the base of a hyperbolic tower, and the warm air column in the tower drives the draft. Kröger's natural-draft direct dry cooling system.

Pack: Natural draft. In the plans: Pro (as its one pack), Expert, Enterprise and Academic. Plans

The analyses it offers

The transient scenarios

  • Step in steam admission (cold start)
  • Ramp to design admission
  • Islanding (settle, then step up)
  • Islanding search: the admission a back-pressure limit allows
  • Step on one boundary channel
  • Step in the ambient temperature
  • The ambient temperature following a profile

What it predicts, and what that was compared with

The app's capability statement for this system, as every report prints it.

AnalysisPredictsCompared withAgreement
Steady rating, and the sweep, design and annual runs built on itAir mass flow rate, heat transfer rate, steam back pressure and every loss of the draft equationThe published design point of the reference towerHeat transfer rate within 0.5%; air mass flow rate 3.5% above the published value
Discretised transientSteam back pressure, tube wall temperature and air mass flow rate through a start-up, a load change or islandingThe CFD co-simulation of the reference tower (Strydom, Pretorius and Laubscher, 2026), run under its own conditions; no measured start-upPeak back pressure 146.8 kPa at 891 s against 142.2 kPa at 850 s; wall peak 383.8 K against 382.9 K; air mass flow rate within 1.1% at 1 500 s; islanding peak 34% low

Its limits

Crosswind on a natural-draft tower is represented by the method of Kröger, Vol. 2, Section 9.2: mean inlet and outlet pressure coefficients in the draft equation and a maldistribution factor on the heat transfer rate, fitted on horizontal bundles filling the inlet. On a vertical ring of deltas the draft-side coefficients carry a multiplier of 0.5, measured on the air mass flow rate of four CFD series. The heat transfer rate lost per unit of air flow is where the CFD literature disagrees, by 0 to 18% from 6 m/s upward, and every report of a windy case states this. Not modelled for this system: fouling that develops in service and degradation (a stated fouling resistance is carried as given), freezing and freeze protection, hybrid or adiabatic inlet assistance, and the plume. Every correlation is a fit over a declared range; the report lists any excursion at the solved state, and a result outside a declared range is an extrapolation and not a prediction.