Kröger Example 8.3.1

A forced-draft bank of six bays

Tier T: a textbook worked example - a published answer, not a measurement.

System: Air-cooled heat exchanger, forced draft

What was compared
The heat transfer rate of a forced-draft bank of six bays of Example 8.1.1 along a 42.3 m platform with two fan rows, and its inlet flow ratio, reduced by flow separation at the platform's inlet edge.
Against
Kröger's worked Example 8.3.1 (Kröger, Vol. 2, Section 8.3, with Salta and Kröger's Eqs. 8.3.1 and 8.3.2), a published calculation and not a measurement.
The agreement
The heat transfer rate of the bank on Kröger's flow-proportional arithmetic is reproduced to −0.039% of his 73.739 MW, and the inlet flow ratio of 0.985 within the case's tolerance of ±0.5%. The model's own heat transfer rate is 74.639 MW, since on this bay a 1.5% cut in air flow costs only 0.26% of the heat transfer rate.
What it shows
The agreement verifies that the model implements Kröger's flow reduction for a forced-draft bank as published. It says nothing about the method's accuracy against a measured bank, and hot-air recirculation between streets is not covered.
Source
Kröger, D.G., Air-Cooled Heat Exchangers and Cooling Towers: Thermal-Flow Performance Evaluation and Design (PennWell, 2004)Vol. 2, Example 8.3.1 (extending Example 8.1.1), Eqs. 8.3.1 and 8.3.2