Skip to the content

The validation record

Carrier 28B Nu-Fin coils (2007): catalogue heating capacities and dry friction against the plate-fin chain

Tier 3: CFD, co-simulation or another model.

System: Dry cooler, plate-fin coil

What was compared
The heating capacity per unit face area and the dry air-side pressure drop of Carrier's 28BH plate-fin water coils of one and two rows at 8, 11 and 14 fins per inch, and the dry air-side friction of its 28BC coils of 4 to 10 rows, rated through the dry cooler's plate-fin chain.
Against
The manufacturer's catalogue ratings from its selection program (Carrier, Form 28B-3PD, 2007, pp. 10, 11, 13 and 35). The document does not state AHRI certification, and the case is Tier 3.
The agreement
On the tube layout the printed water balance supports, the heating capacity lies between −11.8% and +19.8% of the catalogue (mean +8.9%); on the other layout it lies between −27.4% and −3.2% (mean −13.3%). The 28BH dry pressure drops read +13.4% on average, and the 28BC friction reads +50.6% or −42.3% depending on the layout, which the catalogue does not state.
What it shows
The heat side of the plate-fin chain lands within 15% of the manufacturer's capacity on average under either reading of the layout. The loss side cannot be judged until the tube pitches and the fin corrugation are stated, and a catalogue rating is not a measurement of the relations.
Source
Carrier Corporation, 'Nu-Fin coils 28BC, BH, BB, BD, BF, BX, BZ: product data', Form 28B-3PD, 2007p. 13 (28BH heating capacities, notes on the rating condition and the coil it is based on), p. 10-11 (28BH construction: 1/2 in tubes, 0.016 in wall, 8/11/14 fins per inch, 1 or 2 rows, 2.5 in height increments), p. 35 (28BC 1/2 in cooling coil air friction)